330017948
|
1032500
|
2011-03-22
|
750 CANFIELD AVE., COEUR D ALENE, ID, 83815
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2011-03-23
|
Emphasis |
N: AMPUTATE
|
Case Closed |
2011-05-24
|
Related Activity
Type |
Complaint |
Activity Nr |
1467 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001 |
Citaton Type |
Serious |
Standard Cited |
19100333 A01 |
Issuance Date |
2011-04-19 |
Abatement Due Date |
2011-04-26 |
Current Penalty |
3700.0 |
Initial Penalty |
6300.0 |
Final Order |
2011-05-09 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee works on or near them. a) Distribution Panel #3: On or about March 22, 2011 and at times prior thereto, employees were permitted to work on the 480 volt, 3000 amp Meltroom 4 bucket without it being deenergized. Note: Abatement certification and supporting documentation are required for this item. |
|
Citation ID |
01002 |
Citaton Type |
Serious |
Standard Cited |
19100335 A01 I |
Issuance Date |
2011-04-19 |
Abatement Due Date |
2011-04-26 |
Current Penalty |
3650.0 |
Initial Penalty |
6300.0 |
Final Order |
2011-05-09 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed. a) Distribution Panel #3: On or about March 22, 2011 and at times prior thereto, employees performed maintenance on the energized 480 volt, 3000 amp Meltroom 4 bucket without proper personal protective equipment. Note: Abatement certification and supporting documentation are required for this item. |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100335 A02 I |
Issuance Date |
2011-04-19 |
Abatement Due Date |
2011-04-26 |
Current Penalty |
3650.0 |
Initial Penalty |
6300.0 |
Final Order |
2011-05-09 |
Nr Instances |
1 |
Nr Exposed |
2 |
Related Event Code (REC) |
Complaint |
Gravity |
10 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.335(a)(2)(i): Each employee did not use insulated tools or handling equipment if the tools or handling equipment might make contact with such conductors or parts when working near exposed energized conductors or circuit parts. a) Distribution Panel #3: On or about March 22, 2011 and at times prior thereto, employees performed maintenance on the energized 480 volt, 3000 amp Meltroom 4 bucket without insulated tools. Note: Abatement certification and supporting documentation are required for this item. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100037 B06 |
Issuance Date |
2011-04-19 |
Abatement Due Date |
2011-05-10 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2011-05-09 |
Nr Instances |
2 |
Nr Exposed |
180 |
Related Event Code (REC) |
Complaint |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1910.37(b)(6): Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color. a) Meltroom: On or about March 22, 2011 and at times prior thereto, the exit sign over the meltroom door was not illuminated by a reliable light source. The nearest emergency light was approximately 48 feet away. b) Packaging: On or about March 22, 2011 and at times prior thereto, two direction exit signs were not illuminated by a reliable light source. There was no emergency light within a line of sight of the exit signs. Note: Abatement certification is required for this item. |
|
|
311579130
|
1032500
|
2008-10-06
|
750 W. CANFIELD AVE., COEUR D'ALENE, ID, 83815
|
|
Inspection Type |
Complaint
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2008-10-07
|
Emphasis |
S: STRUCK-BY, S: POWERED IND VEHICLE, S: ELECTRICAL, S: NOISE, S: AMPUTATIONS, N: AMPUTATE
|
Case Closed |
2008-12-30
|
Related Activity
Type |
Complaint |
Activity Nr |
200248052 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19100037 A03 |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-11-24 |
Current Penalty |
1050.0 |
Initial Penalty |
1050.0 |
Nr Instances |
1 |
Nr Exposed |
120 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19100037 B04 |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-11-24 |
Nr Instances |
1 |
Nr Exposed |
120 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
01001C |
Citaton Type |
Serious |
Standard Cited |
19100037 D01 |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-11-24 |
Nr Instances |
1 |
Nr Exposed |
120 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
01002A |
Citaton Type |
Serious |
Standard Cited |
19100147 C04 I |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Current Penalty |
1750.0 |
Initial Penalty |
1750.0 |
Nr Instances |
1 |
Nr Exposed |
5 |
Related Event Code (REC) |
Complaint |
Gravity |
03 |
|
Citation ID |
01002B |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 IB |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Nr Instances |
1 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
03 |
|
Citation ID |
01002C |
Citaton Type |
Serious |
Standard Cited |
19100147 C07 IC |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Nr Instances |
1 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
03 |
|
Citation ID |
01003 |
Citaton Type |
Serious |
Standard Cited |
19100253 B02 II |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-11-24 |
Current Penalty |
1050.0 |
Initial Penalty |
1050.0 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19100138 B |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
02002 |
Citaton Type |
Other |
Standard Cited |
19100157 C01 |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Nr Instances |
1 |
Nr Exposed |
120 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
02003 |
Citaton Type |
Other |
Standard Cited |
19100176 A |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Nr Instances |
1 |
Nr Exposed |
120 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
02004 |
Citaton Type |
Other |
Standard Cited |
19100217 B07 III |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-11-24 |
Nr Instances |
1 |
Nr Exposed |
8 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
Citation ID |
02005 |
Citaton Type |
Other |
Standard Cited |
19100334 A02 II |
Issuance Date |
2008-11-20 |
Abatement Due Date |
2008-12-09 |
Nr Instances |
1 |
Nr Exposed |
1 |
Related Event Code (REC) |
Complaint |
Gravity |
01 |
|
|