Inspection Type |
Referral
|
Scope |
Partial
|
Safety/Health |
Safety
|
Close Conference |
2012-05-17
|
Case Closed |
2012-07-17
|
Related Activity
Type |
Referral |
Activity Nr |
367248 |
Safety |
Yes |
|
Type |
Inspection |
Activity Nr |
444975 |
Safety |
Yes |
|
Type |
Inspection |
Activity Nr |
445196 |
Safety |
Yes |
|
Violation Items
Citation ID |
01001A |
Citaton Type |
Serious |
Standard Cited |
19260403 I02 I |
Issuance Date |
2012-06-21 |
Abatement Due Date |
2012-07-13 |
Current Penalty |
0.0 |
Initial Penalty |
1600.0 |
Final Order |
2012-07-12 |
Nr Instances |
4 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph. (a) Main floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around an energized 240 volt power panel. (b) Main floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around an energized 120 volt lighting panel. (c) West side of the second floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around the energized power panel (120V) with a cardboard cover labeled "Hot! Stay Out! (d) East side of the second floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around the energized power panel (120V) with a cardboard cover labeled "Hot! Stay Out! Note: Abatement certification is required for this item. |
|
Citation ID |
01001B |
Citaton Type |
Serious |
Standard Cited |
19260405 D |
Issuance Date |
2012-06-21 |
Abatement Due Date |
2012-07-13 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2012-07-12 |
Nr Instances |
4 |
Nr Exposed |
5 |
Gravity |
5 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.405(d): Panelboards mounted in cabinets, cutout boxes or enclosures designed for the purpose were not dead front: (a) Main floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around an energized 240 volt power panel. (b) Main floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around an energized 120 volt lighting panel. (c) West side of the second floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around the energized power panel (120V) with a cardboard cover labeled "Hot! Stay Out! (d) East side of the second floor of the building, on or about May 17, 2012, and at times prior thereto, as the creating employer, EDA Electric did not protect its employees and other unqualified site workers, in that they were not restricted from entering the area around the energized power panel (120V) with a cardboard cover labeled "Hot! Stay Out! Note: Abatement certification is required for this item. |
|
Citation ID |
02001 |
Citaton Type |
Other |
Standard Cited |
19260403 B02 |
Issuance Date |
2012-06-21 |
Abatement Due Date |
2012-07-13 |
Current Penalty |
0.0 |
Initial Penalty |
0.0 |
Final Order |
2012-07-12 |
Nr Instances |
1 |
Nr Exposed |
2 |
FTA Current Penalty |
0.0 |
Citation text line |
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: (a) Main floor of the building, on or about May 17, 2012, and at times prior thereto, as the exposing employer, EDA Electric did not prevent employees from using a four-way power supply, for charging batteries and for power, that did not meet the electrical code. Note: Abatement certification is required for this item. |
|
|